Compliance Reports
Grid code compliance monitoring and reporting
Voltage THD
2.3%
Limit: < 5%
Current THD
3.1%
Limit: < 5%
Frequency Deviation
±0.02 Hz
Limit: ±0.5 Hz
Voltage Deviation
+8.2%
Limit: ±10%
Power Factor
0.98
Target: > 0.95
Flicker Severity
0.4
Limit: < 1.0
Compliance Score Trend
Overall
Voltage
Frequency
Harmonics
Parameter Compliance Status
Voltage Range
Current
1.02 pu
Min/Max
0.95/1.05
Status
OK
Frequency Range
Current
50.02 Hz
Min/Max
49.5/50.5
Status
OK
Ride Through
Events
3
Success
100%
Status
OK
Reactive Power
Current
12 MVAR
Limit
±15 MVAR
Status
WARN
Voltage Unbalance
Current
0.8%
Limit
< 2%
Status
OK
Response Time
Actual
1.2 sec
Required
< 2 sec
Status
OK
Recent Compliance Violations
| Timestamp | Parameter | Standard | Violation | Duration | Severity | Resolution |
|---|---|---|---|---|---|---|
| 2025-01-19 08:45:23 | Voltage THD | IEEE 519-2014 | 5.8% (Limit: 5%) | 12 min | Warning | Auto-corrected |
| 2025-01-17 14:20:15 | Frequency | NERC PRC-024-3 | 49.4 Hz (Min: 49.5 Hz) | 3 min | Violation | Grid event |
| 2025-01-16 03:12:45 | Power Factor | IEEE 1547-2018 | 0.93 (Min: 0.95) | 45 min | Warning | VAR adjustment |
| 2025-01-14 11:30:00 | Voltage | EN 50160 | 1.12 pu (Max: 1.10 pu) | 8 min | Warning | Tap change |
| 2025-01-12 22:15:30 | Harmonics 5th | IEC 61000-3-2 | 4.2% (Limit: 4%) | 25 min | Warning | Filter activated |